Norden's Maxpower Series 3 kVA UPS is an online double conversion UPS that features a single phase in both input and output, and an output power factor of 0.9. This tower-type UPS is designed to be used in commercial buildings and offices, and can be connected to desktops and servers
Norden's Maxpower Series 3 kVA UPS is an online double conversion UPS that features a single phase in both input and output, and an output power factor of 0.9. This tower-type UPS is designed to be used in commercial buildings and offices, and can be connected to desktops and servers
GENERAL FEATURES
|
Model | CN7003MPI/CN7003MPE | ||
Capacity | VA | 3000 | |
Watts | 2700 | ||
Phase | Single phase with ground | ||
Input | Normal Voltage | 208/220/230/240Vac | |
Operating Voltage Range | 110~300Vac | ||
Frequency Range | 45~55Hz/55~65Hz (Auto-detect) | ||
Power Factor | ≥0.99 @Nominal voltage(100% load) | ||
Output | Output Voltage | 208/220/230/240Vac | |
Power Factor | 0.9 | ||
Voltage Regulation | ±1% | ||
Frequency | Line mode | 46~54Hz / 56~64Hz | |
Bat. mode | 50Hz / 60Hz ±0.1Hz | ||
Crest Factor | 3:1 | ||
Harmonic Distortion (THDv) | ≤3% THD(Linear load) | ||
≤5% THD(Non-linear load) | |||
Transfer time | AC to DC | Zero | |
Inverter to bypass | 4ms(Typical) | ||
Waveform | Pure sinewave | ||
Efficiency | AC Mode | 91% | |
Battery Mode | 88% | ||
Battery | Internal | Battery Type | 12V/9AH |
Numbers | 6 | ||
Typical Recharging Time | 4 hours recover to 90% capacity | ||
Charging current(max.) | 1A | ||
Charging Voltage | 82.2Vdc ±1% | ||
Battery | External | Battery Numbers | 8 |
Charging Voltage | 109.6Vdc ±1% | ||
Charging Current | 12A | ||
Indicators | LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators | |
Alarm | Battery Mode | Beeping every 4 seconds | |
Battery Low | Beeping every second | ||
Overload | Beeping twice every second | ||
Fault | Continuously beeping | ||
Physical | Dimension W x D x H (mm) | Standard model | 191x460x337 |
Long run model | 191x460x337 | ||
Weight (kg) | Standard model | 25 | |
Long run model | 10 | ||
Environment | Humidity | 20-95% RH @ 0-40°C (Non-condensing) | |
Noise level | <50dB @ 1 Meter | ||
Management | Smart RS232/USB | Supports Windows® 7/8/10, Linux, FreeBSD and MAC | |
Optional SNMP | Power management from SNMP manager and web browser | ||
Standards | Safety | IEC/EN62040-1,IEC/EN62477-1 | |
EMC | IEN/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8,IEC61000-4-11,IEC61000-2-2 |
Specifications are subject to change without prior notice
EXTERNAL BATTERY PACK | ||
Model | CNBC00396CT | |
BATTERY SYSTEM | ||
Battery Type | VRLA (Valve Regulated Lead Acid Battery - SMF) | |
Typical battery recharging time | 6~8 hours (to 90% of full capacity) | |
Typical Battery Life | 3~5 years, depend on discharging cycle and ambient temperature | |
System voltage | 96Vdc | |
Charging current (Max) | 1.4A | |
Battery quantity | 16 | |
Capacity | 9Ah/12V (7Ah/12V optional | |
PHYSICAL | ||
Dimension W x D x H (mm) | 191 x 460 x 337 | |
Net weight(kg) | 47.5 | |
ENVIRONMENT | ||
Operating environment | 0°C~40°C | |
Relative humidity | 0~95% (Non condensing) | |
Noise Level | <40dB at 1 Meter |
Part Number | Description | ||
CN7003MPI | 3kVA Online Transformerless UPS (Internal battery) | ||
CN7003MPE | 3kVA Online Transformerless UPS (External battery) | ||
CNBC00396CT | 96VDC Tower Mount Battery Pack |
Part Number | Description | ||
CNS02 | Mini SNMP Card for 1-10kVA UPS |