Norden's Maxpower Series 10 kVA UPS is an online double conversion UPS that features a single phase in both input and output, and an output power factor of 0.9. This has a tower type design to be used in workstations and critical equipment.
Norden's Maxpower Series 10 kVA UPS is an online double conversion UPS that features a single phase in both input and
output, and an output power factor of 0.9. This has a tower type design to be used in workstations and critical equipment.
GENERAL FEATURES
|
Model | CN7010MPI/CN7010MPE | |
Capacity | VA | 10000 |
Watts | 9000 | |
Input | Normal Voltage | 220/230/240Vac |
Operating Voltage Range | 120~276Vac | |
Operating Frequency Range | 40~70Hz (50/60Hz Auto-Sensing) | |
Power Factor | ≥0.99 | |
Bypass voltage range | Max.voltage:230~264Vac Min.voltage:176~220Vac | |
ECO Range | Same as the bypass | |
Harmonic distortion (THDi) | <3%(100% linear load) | |
Generator Input | Support | |
Output | Rated voltage | 220/230/240Vac |
Power Factor | 0.9 | |
Voltage Regulation | ±1% | |
Freq. Line mode | ±10% of the rated frequency | |
Freq. Bat. mode | 50/60(±0.1)Hz | |
Crest Factor | 3:1 | |
Harmonic Distortion (THDv) | ≤2% with linear load, ≤5% with non-linear load | |
Efficiency | >93.5% | |
Waveform | Pure Sine Wave | |
Battery | Battery Voltage | 192/216/240Vdc (Adjustable) (Standard unit 240Vdc) |
Capacity (Standard unit) | 9Ah/12V (7Ah/12V optional) | |
Typical recharging Time | 6~8 hours (to 90% of full capacity) | |
Charging current | 1.35A(Standard unit); Long run unit Max.current 8A(charging current can be set according to battery capacity installed) | |
System features | Transfer time | Mains to battery:0ms; Mains to bypass:0ms |
Overload Line mode | Load≤105% long time running; ≤125% last 10min; ≤130% last 30s; >130% turn to bypass mode immediately | |
Bypass mode | 63A(Breaker) | |
Short circuit | Hold whole system | |
Overheat | Line mode: Turn to bypass; Backup mode: shut down UPS immediately | |
Battery low | Alarm and switch off | |
Self-diagnostics | Upon power on and software control | |
Battery | Advanced battery management | |
Audible & Visual alarms | Line failure, Battery under voltage, Overload, System fault | |
LED and LCD Display | Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault | |
LCD Display | Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time | |
Communication interface | RS232, USB,SNMP card(optional), Relay card (optional)
| |
Environment | Operating temperature | 0~40°C |
Storage temperature | -25~55°C | |
Humidity range | 20~95% (Non-condensing) | |
Altitude | <1500m | |
Noise Level | <58dB | |
Standards | Safety | IEC/EN62040-1,IEC/EN62477-1 |
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8,IEC61000-4-11,IEC6100-2-2 | |
Physical | Dimension | I:191 x 460 x 720 E:191 x 460 x 337 |
Weight | 71 13.5 |
Specifications are subject to change without prior notice
EXTERNAL BATTERY PACK | |
Model | CNBC06120CT |
BATTERY SYSTEM | |
Battery Type | VRLA (Valve Regulated Lead Acid Battery - SMF) |
Typical battery recharging time | 6~8 hours (to 90% of full capacity) |
Typical Battery Life | 3~5 years, depend on discharging cycle and ambient temperature |
System Voltage | 240Vdc |
Battery Qty | 2*20 pcs |
Capacity | 7Ah/9Ah (12V) |
PHYSICAL | |
Dimension(WxDxH) | 250 x 597 x 616 |
Net weight(kg) | 122/134 |
ENVIRONMENT | |
Operating environment | 0°C~40°C |
Relative humidity | 0~95% (Non condensing) |
Noise Level | <40dB at 1 Meter |
Part Number | Description | ||
CN7010MPI | 10kVA Medium Power Transformerless UPS (Internal battery) | ||
CN7010MPE | 10kVA Medium Power Transformerless UPS (External battery) | ||
CNBC10120CT | 120 VDC Battery Pack |
Part Number | Description | ||
CNS02 | SNMP Card |