1kVA Online Transformerless UPS

Norden's Maxpower Series 1 kVA UPS is an online double conversion UPS that features a single phase in both input and output, and an output power factor of 0.9. This tower-type UPS is designed to be used in commercial buildings and offices, and can be connected to desktops and servers.

Norden's Maxpower Series 1 kVA UPS is an online double conversion UPS that features a single phase in both input and output, and an output power factor of 0.9. This tower-type UPS is designed to be used in commercial buildings and offices, and can be connected to desktops and servers.

GENERAL FEATURES

  •  Online double conversion with full digital control
  •  High power density
  • Built-in EMI Filter and Surge Protection
  • Selectable output voltage:220/230/240Vac
  • Wide input voltage range:110~300Vac
  • Input power factor 0.99 with PFC
  • Maximum charging current up to 12A (long run unit)
  • Emergency power off function
  • ECO mode operation for energy saving
  • Multiple communication interface:RS232 (USB/Dry contact/SNMP card optional)
  • Self-testing when UPS start-up
  • Generator compatible 
  • Cold start
  • Intelligent fan speed regulation 


ModelCN7001MPI/CN7001MPE

Capacity

VA

1000

Watts

900

Phase

Single phase with ground

Input

Normal Voltage

208/220/230/240Vac
Operating Voltage Range
110~300Vac

Frequency Range

45~55Hz/55~65Hz (Auto-detect)

Power Factor

≥0.99 @Nominal voltage(100% load)

Output

Output Voltage

208/220/230/240Vac

Power Factor

0.9

Voltage Regulation

±1%

Frequency

Line mode
(Synchronized range)

46~54Hz / 56~64Hz

Bat. mode

50Hz / 60Hz ±0.1Hz

Crest Factor

3:1

Harmonic Distortion (THDv)

≤3% THD(Linear load)

≤5% THD(Non-linear load)

Transfer time

AC to DC

Zero

Inverter to bypass

4ms(Typical)

Waveform

Pure sinewave

Efficiency

AC Mode

88%

Battery Mode

85%

Battery

Internal

Battery Type

12V/9AH

Numbers

3

Typical Recharging Time

4 hours recover to 90% capacity

Charging current(max.)

1A

Charging Voltage

41.1Vdc ±1%

Battery

External

Battery Numbers

3

Charging Voltage

41.1Vdc±1%

Charging Current

12A

Indicators

LCD 

Load level, Battery level, AC mode, Battery mode, Bypass mode, and Fault indicators

Alarm

Battery Mode

Beeping every 4 seconds

Battery Low

Beeping every second

Overload

Beeps twice p second

Fault

Continously beeping

Physical

Dimension

W x D x H (mm)

Standard model

144x293x209/144x399x209

Long run model

144x293x209

Weight

Standard model

9.3/12.5

Long run model

4.1

Environment

Humidity

20-90% RH @ 0-40°C (Non-condensing)

Noise level

<50dB @ 1 Meter

IP RatingIP 20

Management

Smart RS232/USB

Supports Windows® 7/8/10, Linux, FreeBSD and MAC

Optional SNMP

Power management from SNMP manager and web browser

Standards

Safety

CE; IEC/EN62040-1,IEC/EN62477-1

EMC

IEN/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8,IEC61000-4-11,IEC61000-2-2

Specifications are subject to change without prior notice


EXTERNAL BATTERY PACK

ModelCNBC00136CT
BATTERY SYSTEM

Battery Type

VRLA (Valve Regulated Lead Acid Battery - SMF)

Typical battery recharging time
6~8 hours (to 90% of full capacity)
Typical Battery Life3~5 years, depend on discharging cycle and ambient temperature

System Voltage

24Vdc

36Vdc

Charging current (Max)1.4A1.4A
Battery quantity46

Capacity

9Ah/12V (7Ah/12V optional

PHYSICAL

Dimension W x D x H (mm)144 x 399 x 209
Net weight(kg)9.3
ENVIRONMENT

Operating environment
0°C~40°C
Relative humidity
0~95% (Non condensing)
Noise Level<40dB at 1 Meter

                                                                     

Part NumberDescription

CN7001MPI

1kVA Online Transformerless UPS (Internal battery) 

CN7001MPE

1kVA  Online  Transformerless UPS (External battery) 

CNBC00124CT

24VDC Tower Mount Battery Pack

CNBC00136CT

36VDC Tower Mount Battery Pack

COMPATIBLE ACCESSORIES

Part NumberDescription
CNS02