PH 120 STRANDED CONDUCTOR PAIRED FIRE RESISTANT CABLE

NORDEN FireNor PH120 stranded Conductor twisted pair fire resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, hotels etc. FireNor products have low smoke density, are halogen free and they don't emit poisonous gases.

NORDEN FireNor PH120 stranded Conductor twisted pair fire resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, hotels etc. FireNor products have low smoke density, are halogen free and they don't emit poisonous gases.

CABLE CONSTRUCTION




Flame TestsCircuit Integrity
Smoke DensityCorrosive Gases  MeasurementOther Stanaderds

IEC 60332-1
IEC 60332-3-24

IEC 60331-21
EN 50200 PH 120 (120 Min)
BS 6387 C, W, Z
Cat,C fire @950°C - 180 min
Cat,W fire and water @ 650°C
-15 +15 min
Cat,Z fire and mechanical shocks @ 950°C - 15 min

(UL 2196 (2hRS))

IEC 61034-1/2

IEC 60754-1/2

NFPA 70,72 & 101

IEC 60228 


ELECTRICAL & MECHANICAL CHARACTERISTICS

PropertiesValue
1.0 mm²2.5 mm²

Max. Conductor Resistant @ 20ºC

12.1 Ω/km

7.55 Ω/km

Min. Insulation Resistant @ 20ºC

200 MΩxkm

Operating Voltage

300/500 V

Test Voltage

2000 V

Temperature Range (Operation)

-30ºC to + 90ºC

Temperature Range (Installation)

-10ºC to + 90ºC

Min. Bend Radius (Flexing)

8 x D

Min. Bend Radius (Flexing)
15 x D


PHYSICAL INFORMATION


No. of Pairs / Cond.Cross 2 Section (mm²)Insulation Diameter ( mm )
Cable Diameter ( mm ) 
Weight ( Kg/100m) 
1 X 1.5 
3.40
8.60
9.00
1 X 2.5
4.10
10.50 
13.50 
2 x 1.5
3.40 
13.8 ± 0.2
18.00
2 × 2.5
4.10
16.0±0.1 
24.20
Part NumberDescription
6J-1501X
PH120 Stranded Conductor Paired Fire Resistant Cable, 1P X 1.5 mm²
6J-2501X
PH120 Stranded Conductor Paired Fire Resistant Cable, 1P X 2.5 mm² 
6J-1502X
PH120 Stranded Conductor Paired Fire Resistant Cable, 2P X 1.5 mm²
6J-2502X
PH120 Stranded Conductor Paired Fire Resistant Cable, 2P X 2.5 mm²

X > RD: Red