CAT 6A F/FTP 4 PAIR 23 AWG STEEL WIRE ARMOURED CABLE LSZH

Norden Category 6A F/FTP Steel Wire Armoured cables exceed Category 6A / Class EA specification. It is tested to 500 MHz frequency range and designed to support 10 Gigabyte and External applications to full 100 m. Extremely high pair-balance providing excellent EMC (Electro Magnetic compatibility), minimizing radiation, maximizing noise immunity and providing high alien cross talk performance to F/FTP cabling systems. F/FTP (Twisted Pair – overall and individual Foil shield) cabling systems are installed for improved Alien Cross talk performance.

Norden Category 6A F/FTP Steel Wire Armoured cables exceed Category 6A / Class EA specification. It is tested to 500 MHz frequency range and designed to support 10 Gigabyte and External applications to full 100 m. Extremely high pair-balance providing excellent EMC (Electro Magnetic compatibility), minimizing radiation, maximizing noise immunity and providing high alien cross talk performance to F/FTP cabling systems. F/FTP (Twisted Pair – overall and individual Foil shield) cabling systems are installed for improved Alien Cross talk performance.




MATERIAL CONSTRUCTION & DESIGN

Conductor MaterialBare Copper
Conductor Size0.56 mm, 23 AWG
Conductor ConstructionSolid
Insulation MaterialSFS PE
Insulation O.D.1.33 mm nom.
Conductor Unit IdentificationSolid/Stripe
Colour CodePer TIA/EIA 568-B
In. Shield MaterialAluminium/Polyester Foil
In. Shield Design100 % Coverage
Overall Shield Design100 % Coverage
Overall Foil ShieldYes
Overall Shield MaterialAluminium/Polyester Foil
Overall Drain-Wire MaterialTinned Copper
Overall Drain-Wire Size0.41 mm
Overall Drain-Wire Construction Solid
Total number of Wires 
8
Inner Sheath Material
LSZH 
Inner Sheath Thickness 
0.80±0.2 mm
Armored Material
Steel Wires
Outer Jacket MaterialFR-LSZH 
Outer Jacket Thickness1.1±0.4 mm
Outer Jacket Diameter
11.4±1.0 mm
Rip Cord
Yes
Outer Jacket Colour
Per Requirement
Marking
Per Requirement


ELECTRICAL & MECHANICAL CHARACTERISTICS

Frequency Range
1 - 500 MHz
Impedance 100 Ω
Coupling Attenuation85 dB min @ 30-100 MHz 85-20Log (f/100) @100-500 MHz
DC Resistance78 Ω/km nom.
Max. Resistance Unbalance 2 %
Capacitance Unbalance1.2 pF/m max.
Velocity of Propagation 80 % nom.
Propagation Delay Skew25 ns/100m max.
Dielectric Strength1.5 KV/minute
Dielectric Strength to Shield1.5 KV/minute
Min. Insulation Resistance5 GΩ•km
Transfer Impedance1000 mΩ/m max. @ 100 MHz.
Max. Tensile Strength - Short Term130 N
Min. Bend Radius 50 mm 
Operating Temperature Range -20 °C +60 °C



TRANSMISSION PERFORMANCE

Cat. 6 Un-screened Pair Horizontal Cables*
Freq.
MHz
Attenuation
dB/100m @ 20ºC
NEXT
dB
PSNEXT
dB
RL
dB
ELFEXT
dB
PSELFEXT
dB
13.065.062.019.164.261.2
43.564.1 61.821.0 52.149.1
85.0
59.4
57.0
21.0 
46.1 
43.1
105.457.8
55.521.044.241.2 
167.0
54.6
52.2
20.0
40.1 
37.1 
207.9
53.150.719.538.2 35.2
258.9
51.5
49.1
19.0 
36.2
33.2 
31.2510.0
50.0
47.5
18.5
34.3
31.3 
62.514.4
45.1
42.7
16.0
28.3
25.3 
10018.6
41.839.314.0 24.221.2
20027.4
36.934.311.0 18.215.2 
25031.1 
35.332.710.0 16.213.2 
40038.4
29.927.1 8.0 12.1 9.1 
50043.8
26.723.88.0 10.27.2 

Part NumberDescriptionStandard Length
114-20622404X
Cat 6A F/FTP 4 Pair 23 AWG Steel Wire Armoured Cable LSZH
305 mtr

X: BK(Black), BL(Blue), GN(Green), GY(Gray), RD(Red), WH(White), YL(Yellow)