10-30KVA DOUBLE CONVERSION TRANSFORMER-BASED UPS

Norden's Ultra power series 10-30kVA UPS is an online Transformer-based UPS which has three phase in both input and output and an output power factor of 0.9.This UPS Features an isolation transformer in the output side to provide galvanic isolation for the load connected and parallel operation helps to increase redundancy and capacity.

Norden's Ultra power series 10-30kVA UPS is an online Transformer-based UPS which has three phase in both input and output and an output power factor of 0.9.This UPS Features an isolation transformer in the output side to provide galvanic isolation for the load connected and parallel operation helps to increase redundancy and capacity.

GENERAL FEATURES

    • Online Double Conversion
    • Full DSP Control
    • High Power Factor
    • Wide input adaptability
    • Optimized battery management
    • N+X parallel redundancy
    • Strong overload capability
    • Multi-protection
    • Generator mode
    • EPO function 


    Specification

    ModelCN43310TU 
    CN43320TU 
    CN43330TU 

    Capacity

    kVA

    10kVA

    20kVA
    30kVA

    Watts

    9kW

    18kW
    27kW

    Input

    Normal Voltage380/400/415Vac (3Ph+N+PE) (-25% +20%)
    Operating frequency range
    50/60Hz (±5Hz) 
    Power factor
    ≥0.97 (with
    Bypass voltage range

    Upper limit:+20%(+10%,+15%,+20% adjustable)

    Lower limit:-40%(-10%,-20%,-30%,-40% adjustable)

    Bypass Frequency range
    ±10%(±2.5%,±5%,±10%,±20% adjustable)

    Output

    Rated voltage380/400/415Vac (3Ph+N+PE)
    Power factor
    0.9
    Voltage regulation
    ±1%
    Frequency   
    50/60(±0.05)Hz
    Crest factor
    3:1
    Harmonic distortion (THDv)
    ≤2% with linear load
    Efficiency
    >88%                                                                           >89%
    Output Waveform
    Pure Sine Wave

    Battery

    Battery voltage384Vdc (30/32pcs)

    Charging Current9.1A                                      18.2A                                27.3A     

    System Features

    Transfer timeMains to battery:0ms; Mains to bypass:0ms
    Overload  
    ≤110%: Overload 60min, ≤150%: Overload 1min, >150% turn to bypass mode immediately
    LED Display
    Input, Inverter, Bypass, Battery, Output, Status 
    LCD Display 
    I/O voltage, frequency, power, power factor, battery voltage, current, battery status, load percentage, UPS status, history record, settings
    Communication 
    USB, RS232, RS485, Parallel port, dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional)

    Environment

    Operating temperature0~40°C
    Storage temperature
    -25~55°C
    Humidity range
    0~95% (Non-condensing)
    Altitude
    <1500m
    Noise level
    <58dB

    Physical

    Dimension WxDxH(mm)350x650x1050
    Net Weight (kg)
    145165204

    Standards

    SafetyIEC/EN62040-1,IEC/EN62477-1
    EMC

    IEC/EN 62040-2;IEC 61000-2-2;IEC 61000-4-2;IEC 61000-4-3;IEC 61000-4-4 IEC 61000-4-5;IEC 61000-4-6;IEC 61000-4-8;IEC 61000-4-11 2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

    Performance
    IEC62040-3


                                                                          

    Part NumberDescription
    CN43310TU
    10kVA Double Conversion Transformer-Based 3/3 UPS(External Battery)
    CN43320TU
    20kVA Double Conversion Transformer-Based 3/3 UPS (External Battery)
    CN43330TU 
    30kVA Double Conversion Transformer-Based 3/3 UPS (External Battery)

    COMPATIBLE ACCESSORIES

    Part NumberDescription
    CNS01
    SNMP Card