30-40KVA DOUBLE CONVERSION TRANSFORMER-LESS UPS

Norden's Ultra power series 30-40 kVA UPS is an online double conversion UPS that features three-phase in both input and output and an output power factor of 0.9 This tower model features a high-density design with parallel redundancy and ECO mode for power savings.

Norden's Ultra power series 30-40 kVA UPS is an online double conversion UPS that features three-phase in both input and output and an output power factor of 0.9 This tower model features a high-density design with parallel redundancy and ECO mode for power savings.

General Features

  • High power density design
  • N+X parallel redundancy, support maximum 4 units in parallel
  • Online double conversion with DSP control
  • Input current harmonic:<3%
  • Wide input voltage range:208~478Vac
  • Wide input frequency range:40~70Hz
  • Optimization battery group, the quantity of battery: 30~50pcs
  • Maximum charging current up to 20A
  • Generator compatible
  • ECO mode operation for energy saving
  • Intelligent fan speed regulation
  • Self-testing when UPS startup
  • 50/60Hz frequency converter mode

Specification

ModelCN93330U
CN93340U

Capacity

kVA

30

40

Watts

27kW

36kW

Input

Normal Voltage380/400/415Vac (3Ph+N+PE)
Operating voltage range
305~478Vac(Full load); 208~478Vac(50% load)
Harmonic distortion(THDi) 
<3%(100% linear load)
Operating frequency range
40~70Hz (50/60Hz Auto-Sensing)
Power factor
≥0.99
Bypass voltage range

220Vac Max.Voltage:+25% (optional +10%,+15%,+20%) 230Vac Max.Voltage:+20%(optional +10%,+15%)

240Vac Max.Voltage:+15%(optional +10%) Min.Voltage:-45%(optional -20%,-30%)

Bypass Frequency range
Frequency synchronize tracing range:±10%
Generator input
Support

Output

Rated voltage380/400/415Vac (3Ph+N+PE)
Power factor
0.9
Voltage regulation
±1%
Frequency                            Line mode
±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional)
Frequency                            Bat. mode
50/60(±0.1)Hz
Crest factor
3:1
Harmonic distortion (THDv)
≤2% with linear load, ≤4% with non-linear load
Efficiency
94.5%
Output Waveform
Pure Sine Wave

Battery                                                 

Battery voltage±180/±192/±204/±216/±228/±240/±252/±264/±276/±288/±300Vdc(30/32/34/36/38/40/42/44/46/48/50pcs)
Charging current (Charging current can be set according to the battery capacity installed)
20A 

System Features

Transfer timeMains to battery:0ms; Inverter to bypass:0ms
Overload                       Line mode
≤110%,last 60min; ≤125%,last 10min; ≤150%,last 1min;>150% turn to bypass Immediately
Overload                      Bypass mode≤110%,last 10min; ≤125%,last 1min; ≤150%,last 5s;>150% turn to bypass Immediately
Backfeed Protection Support
Alarm
Overload, utility abnormal, UPS fault, battery low, etc
Protection
Short circuit, overload, over-temperature, battery low, fan fault alarm
Remote LCD
Support
Communication
USB, RS232, RS485, Parallel port, dry contact, Intelligent slot, LBS, SNMP card (optional), Relay card (optional) 

Environment

Operating temperature0~40°C
Storage temperature
-25~55°C
Humidity range
0~95% (Non-condensing)
Altitude
<1500m
Noise level
<61dB
<64db

Physical

Dimension WxDxH(mm)250x580x655
Net Weight (kg)
43
46

Standards

SafetyCE; IEC/EN62040-1,IEC/EN62477-1
EMC
IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8


Part NumberDescription
CN93330U30kVA Double Conversion Transformer-less 3/3 UPS (External Battery)
CN93330U-5L
30kVA Double Conversion Transformer-less 3/3 UPS with 5inch LCD display (External Battery)
CN93340U
40kVA Double Conversion Transformer-less 3/3 UPS (External Battery)
CN93340U-5L
40kVA Double Conversion Transformer-less 3/3 UPS with 5inch LCD display (External Battery)


COMPATIBLE ACCESSORIES

Part NumberDescription
CNS01
SNMP Card