NORDEN FireNor Premium fire resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning. emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi- intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas. theatres, schools, shopping centers. airports, factories, hotels etc. FireNor products have low smoke density, are halogen free and they don't emit poisonous gases.
NORDEN FireNor Premium fire resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning. emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi- intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas. theatres, schools, shopping centers. airports, factories, hotels etc. FireNor products have low smoke density, are halogen free and they don't emit poisonous gases.
Flame Tests | Insulation Integrity | Smoke Density | Corrosive Gases & Halogen Free Test | LPCB Stanaderds |
IEC 60332-1-2 |
IEC 60331-23 |
IEC 61034-2 |
IEC 60754-2 |
BS 7629-1:2015 (Standard 60) BS 6387:2013 (Category CWZ) BS 5839-1:2013 (Clause 26.2d Standard) EN 50200:2015 (Class PH120) EN 50200:2015 Annex E EN 60754-2:2014 EN 60332-3-22:2009 |
Properties | Value | |||
1.0 mm² | 1.5 mm² | 2.5 mm² | 4.0 mm² | |
Max. Conductor Resistant @ 20ºC |
18.1Ω/km |
12.1 Ω/km |
7.4 Ω/km |
4.61 Ω/km |
Min. Insulation Resistant @ 0ºC |
200 MΩxkm |
|||
Operating Voltage |
300/500 V |
|||
Test Voltage |
2000 V |
|||
Temperature Rating(Fixed) |
-40ºC to + 70ºC |
|||
Temperature Rating(Flexing) |
-5ºC to + 60ºC |
|||
Min. Bend Radius(Fixed) |
6 x D |
|||
Min. Bend Radius(Flexing) |
15 x D |
Nom. Cond. Cross-Sect. mm² |
Conductor Size no./mm |
Drain Wire Size no./mm | Cable Diameter mm (±5 %) |
Weight Kg/km |
2 x 1.0 |
1/1.12 |
1/1.12 |
6.90 |
77.14 |
2 x 1.5 |
1/1.37 |
1/1.37 |
7.90 |
101.39 |
3 x 1.5 |
1/1.37 |
1/1.37 |
8.20 |
124.46 |
4 x 1.5 |
1/1.37 |
1/1.37 |
9.20 |
156.39 |
2 x 2.5 |
1/1.75 |
1/1.75 |
9.30 |
148.19 |
3 x 2.5 |
1/1.75 |
1/1.75 |
11.0 |
184.4 |
4 x 2.5 |
1/1.75 |
1/1.75 |
10.80 |
229.93 |
2 x 4.0 |
1/2.30 |
1/2.30 |
10.30 |
201.56 |
3 x 4.0 |
1/2.30 |
1/2.30 |
10.40 |
253.33 |
4 x 4.0 |
1/2.30 |
1/2.30 |
12.10 |
315.96 |
Part Number | Description |
66-1002XY |
Premium Fire Resistant Cable EN 50200 PH120, 2C x 1.0mm² |
66-1502XY |
Premium Fire Resistant Cable EN 50200 PH120, 2C x 1.5mm² |
66-1503XY |
Premium Fire Resistant Cable EN 50200 PH120, 3C x 1.5mm² |
66-1504XY |
Premium Fire Resistant Cable EN 50200 PH120, 4C x 1.5mm² |
66-2502XY |
Premium Fire Resistant Cable EN 50200 PH120, 2C x 2.5mm² |
66-2503XY |
Premium Fire Resistant Cable EN 50200 PH120, 3C x 2.5mm² |
66-2504XY |
Premium Fire Resistant Cable EN 50200 PH120, 4C x 2.5mm² |
66-4002XY |
Premium Fire Resistant Cable EN 50200 PH120, 2C x 4.0mm |
66-4003XY |
Premium Fire Resistant Cable EN 50200 PH120, 3C x 4.0mm² |
66-4004XY |
Premium Fire Resistant Cable EN 50200 PH120, 4C x 4.0mm² |
X > BK:Black, RD:Red, WH:White, OR:Orange