EIB BUS CABLE 4 CORE 18 AWG SHIELDED

EIB BUS SYSTEM cables are primarily designed for communication in building management system with the application scope of controlling lighting, air conditioning, blinds, heating and time management, The cables are not suitable for power transmission and direct burial.

EIB BUS SYSTEM cables are primarily designed for communication in building management system with the application scope of controlling lighting, air conditioning,

blinds, heating and time management, The cables are not suitable for power transmission and direct burial.

CABLE CONSTRUCTION


PHYSICAL CHARACTERISTICS

CharacteristicValue

No. of Conductor

4

Conductor Size

18 AWG , 1.024 mm

Insulation Thickness

0.35mm

Insulation Diameter
1.72mm

Drain Wire Size

24 AWG , 0.4 mm

Jacket Thickness

0.9 mm

Jacket Diameter

6.7 mm

Min. Bending Radius Install

67 mm

Operating Temperature

-20ºC to +75ºC

 


ELECTRICAL CHARACTERISTICS

CharacteristicUnitValue

Nom. Conductor DCR @ 20°C

Ω/km

38.5

Dielectric Strength between pairs

kv/min

≥1.0

Short or open of the loop
-None
Shield 
-No break

MECHANICAL CHARACTERISTICS

CharacteristicValue

Test Material

PVC/LSZH

Before Tensile Strength (Mpa)

≥10.0

Aging Elongation (%)

≥125

Aaina Condition (°C x hrs) 
100 x 168

After Tensile Strength (Mpa)

≥8.0

Aging Elongation (%)

≥100

Cold Bend (-20±°C x 4 hrs)

No Crack

INSULATION COLOUR CODE

Individual PairColour

Core 1

Black

Core 2

Red

Core 3

White

Core 4
Green
Part NumberDescriptionLength
81-2304181X
EIB BUS Cable 4 Core 18 AWG Shielded PVC
305 m
81-2304182X
EIB BUS Cable 4 Core 18 AWG Shielded LSZH
305 m