ULTRA-POWER SERIES 100-600kVA Double Conversion Modular UPS

Where the UPS system is divided into independent modules or units. Each module typically contains its own set of components, such as power converters, inverters, and battery systems. These modules can operate independently or be combined to provide a scalable and flexible power protection solution

Where the UPS system is divided into independent modules or units. Each module typically contains its own set of components, such as 

power converters, inverters, and battery systems. These modules can operate independently or be combined to provide a scalable and flexible power protection solution

General Features

  • High reliability
  • High Scalability and Redundancy
  • Hot-swappable power modules and bypass modules.
  • 3-level topology design, efficiency is up to 95.8%.
  • High input power factor, it is up to 0.99
  • THDi<3% (100% linear load).
  • N+X parallel redundancy supports a maximum of 6 units in parallel.
  • Batteries number of each group can be selected from 30 pieces to 50 pieces
  • Output power factor is 1.0, UPS can supply power to 100% unbalanced load.
  • High adaptability for load, it can connect full inductive load or capacitive load.
  • With 7 inches (standard) and 10 inches (optional) colorful touch LCD screen
  • Support SNMP, RS232, RS485, Dry contact interface. 


SPECIFICATIONS


PARAMETERS



Cabinet 
Cabinet capacity kVA
100kVA
150kVA
200kVA
300kVA
400kVA

Module capacity kW


50kW


Max. module number
23468

Input

Normal Voltage380/400/415Vac, (3Ph+N+PE)
Operating voltage range
138~305Vac for 40% load; 305~485Vac for 100% load
Operating frequency range
40Hz~70Hz
Power factor
>0.99
Harmonic distortion (THDi) 
≤3% (100% linear load) 
Bypass voltage range

Max. voltage : 220V: +25% (optional+10%, +15%, +20% ); 230V : +20% (optional +10%, +15% ); 240V : +15% (optional +10%) Min. voltage : -45% (optional-10%, -15%, -20%, -30%)

Bypass Frequency tracking range
±10%
Power walk in
Support 
Generator input
Support 

Output

Rated voltage380/400/415Vac,(3Ph+N+PE)

Power factor
1  
Voltage regulation
±1% 
Output frequency         Line mode 
Synchronize with input, when the input frequency >±10% (±1%/±2%/±4%/±5% optional), output 50/60 (±0.1Hz) 
                                     Batt. mode
(50/60±0.1%)Hz  

Crest factor
03:01 

Harmonic distortion (THDv)
≤1% with linear load; ≤3% with nonlinear load

Efficiency
Up to 96%

Battery

Battery voltage    VRLA Battery          360Vdc~600Vdc (30~50 pcs, 36 pcs default, 36~50 pcs no power derating; 32~34 pcs output power factor 0.9; 30 pcs output power factor 0.8)                                                    
Power module charge current
20A (Max.

System Features

Transfer timeUtility to Battery : 0ms; Utility to Bypass : 0ms
Overload                 Inverter mode
≤110% 60min, ≤125% 10min, ≤150% 1min, 150% 1.2s shut down inverter
                                Bypass mode30°C : 135% for long term; 40C: 125% for long term; >1000%, 100ms
OverheatLine Mode : Switch to Bypass; Backup Mode : Shut down UPS immediately
Low battery voltage
Alarm and Switch off
Self-diagnostics
Upon Power On and Software Control
Backfeed protection
Support 
Battery
Advanced battery management
Noise suppression
Complies with EN62040-3
Audible&visual alarm
Line Failure, Battery Low, Overload, System Fault
Status LED & LCD display
Line Mode, Bypass Mode, Battery Low, Battery Fault, Overload & UPS Fault
Reading on the LCD display
Input, Output, Battery, Command, Setting, Maintenance
Communication Interface
Rs232, RS485, Parallel, LBS, BMS, Dry contact port, Relay card(optional), SNMP card(optional), Battery temperature sensor(optional)

Environment

Operating temperature0~40°C 

Storage temperature
-25~55°C 

Humidity range
0~95% (Non-condensing) 

Altitude
<1500m, derating required when >1500m 

Noise level 
<73dB

Physical

Dimension 

WxDxH (mm)

               UPS cabinet(S/F)

600×850×2000
600×850×2000
600×850×20001200×850×2000
1200×850×2000

               Power Module   440×620×130



Net Weight (kg   

                   UPS cabinet

240 260290480540

                  Power Module
34

Standards

SafetyIEC/EN62040-1, IEC/EN62477-1
EMC
IEC/EN62040-2 (IEC61000-2-2, IEC61000-4-2, IEC61000-4-3, IEC61000-4-4, IEC61000-4-5, IEC61000-4-6, IEC61000-4-8, IEC61000-4-11