Mineral Insulated Light Duty Served Cable

Mineral Insulated Cable delivers Fire Performance. It guarantees data transmission and security of power and control circuits by exceeding the requirements of BS- 8519-1 providing circuit integrity at 950°C. It also exceeds enhanced grade requirements defined by BS 5839-1-26.2e and satisfies all Cat. 1, 2 & 3 power and all Cat. 1, 2 & 3 control requirements defined by BS 8519

Mineral Insulated Cable delivers Fire Performance. It guarantees data transmission and security of power and control circuits by exceeding the requirements of BS- 8519-1 providing circuit integrity at 950°C. It also exceeds enhanced grade requirements defined by BS 5839-1-26.2e and satisfies all Cat. 1, 2 & 3 power and all Cat. 1, 2 & 3 control requirements defined by BS 8519

CABLE CONSTRUCTION

Conductor

Plain Annealed solid Copper

Core Identification

By Sleeve Colour

Sheath Color

Red, White, Orange or Any Other

Insulation

Compressed Magnesium Oxide Power (Organic)

Sheath

Plain Copper Sheath and Plus Thermoplastic LSZH Sheath

Standard Packing Mode

Cut of Length / Reeled




Manufacturing
Standard
Code of Practice /
Guide to use
Fire Tests Emission and Flame
Propagation

BS EN 60702 – 1

BS 5839 – 1 Clause 26.2 Enhanced
BS 5266
BS 8519 Category 1 & 2 Control (For Category 3 & Power Application see special notes)

BS 8434 – 2
BS EN 50200
PH30
PH60
PH120
BS 6387 CWZ
BS 8491

BS EN 50267 (IEC 60754) Acid
Gas Emission
BS EN 50268 (IEC 61034)
Smoke Emission
BS EN 50265/50266 (IEC 60332) Flame Propogation


ELECTRICAL & MECHANICAL CHARACTERISTICS

Properties Value
1.0 mm² 1.5 mm² 2.5 mm² 4.0 mm²

Max. Cond. Resistant @ 20 ºC

18.0 Ω/km

12.1 Ω/km

7.41 Ω/km 4.61 Ω/km

Voltage Rating

500 V (For Light Duty Use)

Min. Bend Radius

6 x D

Operating Temperature

-10 °C to +250 °C (It can withstand up to melting point of copper 1083 °C but this will lead to the reduction of the life of the cable

PHYSICAL INFORMATION

No. of Core x Nom.
(n x mm2)
Nom. CSA of
Copper Sheath
(mm2)
Voltage Rating
(A)
Voltage Drop
(mV)
Outer Diameter
(mm)
Weight
(kg/km)

2 x 1.0

5.40

19.5

42

6.4

126.0

2 x 1.5

6.30

25

28

7.0

154.0

2 x 2.5

8.20

33

17

7.9

206.0

2 x 4.0

10.7

44

10

9.2

322.0

3 x 1.0

6.70

16.5

36

7.0

159.0

3 x 1.5

7.80

21

24

7.7

194.0

3 x 2.5

9.50

28

14

8.8

272.0

4 x 1.0

7.70

16

36

7.6

187.0

4 x 1.5

9.10

21

24

8.3

231.0

4 x 2.5

11.3

28

14

9.6

336.0

7 x 1.5

11.8

14

28

9.9

351.0

7 x 2.5

15.4

19

17

11.2

475.0

Part Number Description

51-L1002X

MI Served LSZH Cable 2C x 1.0  mm² (Light Duty-500V)

51-L1003X

MI Served LSZH Cable 3C x 1.0 mm² (Light Duty-500V)

51-L1004X

MI Served LSZH Cable 4C x 1.0  mm² (Light Duty-500V)

51-L1502X

MI Served LSZH Cable 2C x 1.5  mm² (Light Duty-500V)

51-L1503X

MI Served LSZH Cable 3C x 1.5  mm² (Light Duty-500V)

51-L1504X

MI Served LSZH Cable 4C x 1.5  mm² (Light Duty-500V)

51-L1507X

MI Served LSZH Cable 7C x 1.5  mm² (Light Duty-500V)

51-L2502X

MI Served LSZH Cable 2C x 2.5 mm² (Light Duty-500V)

51-L2503X

MI Served LSZH Cable 3C x 2.5  mm² (Light Duty-500V)

51-L2504X

MI Served LSZH Cable 4C x 2.5 mm² (Light Duty-500V)

51-L2507X

MI Served LSZH Cable 7C x 2.5  mm² (Light Duty-500V)

51-L4002X

MI Served LSZH Cable 2C x 4.0  mm² (Light Duty-500V)

X →RD: Red  WH: White  OR: Orange