The shielded power limited fire protective signal cable from Norden is suitable for installation in signalling & fire alarm systems. It works at a high temperature level. This cable is constructed with FR PVC Insulation, Aluminium – Polyester Foil shield with LSZH outer jacket.
The shielded power limited fire protective signal cable from Norden is suitable for installation in signalling & fire alarm systems. It works at a high temperature level. This cable is constructed with FR PVC Insulation, Aluminium – Polyester Foil shield with LSZH outer jacket.
CABLE CONSTRUCTION
Characteristic | Value |
No. of Conductor | 2 |
Conductor Size | 16 AWG ( 1.29 ± 0.005 mm ) |
Insulation Diameter | 2.1 ± 0.05 mm |
Drain Wire Size | 7 x 0.25 mm |
Jacket Thickness | 0.8 mm |
Jacket Diameter | 6.0 ± 0.3 mm |
Recommended Pulling Tension | 27 KG |
Min. Bending Radius | 10 x OD |
Operating Temperature | -20°C to +60°C |
Characteristic | Value | Unit |
Conductor DC Resistance | Ω/km | 13.7 |
Max. Operating Voltage | V | 300 |
Sparker Test | VAC | 3000 |
Characteristic | Value |
Test Material | LSZH |
Before Tensile Strength (Mpa) | 13.8 |
Aging Elongation (%) | 100 |
After Tensile Strength (Mpa) | 11.8 |
Aging Elongation (% of unaged) | 50 |
Cold Bend (-20±°C x 4 hrs) | No Crack |
PART NUMBER | DESCRIPTION |
75-1202162 | 2 Core 16 AWG Shielded Power Limited Fire Protective Signal Cable LSZH |