Norden Category 6A F/UTP cables exceed Category 6A / Class EA specification. It is tested to 500 MHz frequency range and designed to support 10 Gigabyte applications to full 100 m. Extremely high pair-balance providing excellent EMC (Electro Magnetic compatibility), minimizing radiation, maximizing noise immunity and providing high alien cross talk performance to F/UTP cabling systems. F/UTP (Twisted Pair – overall Foil shield) cabling systems are installed for improved Alien Cross talk performance.
Norden Category 6A F/UTP cables exceed Category 6A /Class EA specification. It is tested to 500 MHz frequency range and designed to support 10 Gigabyte applications to full 100 m. Extremely high pair-balance providing excellent EMC (Electro Magnetic compatibility), minimizing radiation, maximizing noise immunity and providing high alien cross talk performance to F/UTP cabling systems. F/UTP (Twisted Pair – overall Foil shield) cabling systems are installed for improved Alien Cross talk performance.
Product Sequense | Premium |
Product Type | Twisted Pair Cable |
Conductor Material | Solid Bare Electrolytic Grade Copper |
Conductor Size | 23 AWG |
Conductor Construction | Solid |
Conductor Diameter | 0.565 ± 0.01mm |
Insulation Material | PE |
Insulation Diameter | 1.12±0.1 mm |
Conductor Unit Identification | Solid/Stripe |
Colour Code | Per TIA/EIA 568-B |
Screening Material | Mylar+ AL/Mylar |
Conductor Unit Lay-Up | Pairs |
Overall Drain-Wire Material | Tinned copper 0.4mm |
Overall Drain-Wire Construction | Solid |
Total Number of Wires | 8 |
Outer Jacket Material | UV-LSZH |
Outer Jacket Thickness & Ex. Diameter | 0.55±0.05mm, 7.4±0.4 mm |
Rip Cord | Yes |
Outer Jacket Colour | Per Requirement |
Marking | Per Requirement |
Frequency Range | 1 - 500 MHz |
Characteristic Impedance | 100±15Ω(1-250Mhz) 100±22Ω(250-500Mhz) |
Coupling Attenuation | 55 dB min @ 30-100 MHz 55-20 Log (f/100) @100-500 MHz |
DC Resistance | 9.38Ω/m |
DC Conductor Resistance Unbalance | Max.5% |
Capacitance Unbalance | ≤ 330 pF/100m |
Unbalanced-to-ground capacitance | max.330 pf/100m |
Velocity of Propagation | 67% |
Delay Skew | ≤ 45ns/100m |
Dielectric Strength | DC 1000V for 1min |
Min. Insulation Resistance | 5000MΩ•km |
Transfer Impedance | 1000 mΩ/m max @ 100 MHz |
Max. Tensile Strength - Short Term | ≥ 10.0MPa(Before Aging), ≥ 8.0MPa(After Aging) |
Min. Bend Radius | 8*OD-4*OD |
Cold bend (-20±2℃×4h) | 8×Cable OD. No visible cracks |
Operating Temperature Range | -40℃ to +70℃ |
Freq. MHz | RL ≥dB | ATT ≤dB | NEXT ≥dB | PHASE DELAY ≤ns | PSNEXT ≥dB | ELFEXT ≥dB | PSELFEXT ≥dB |
---|---|---|---|---|---|---|---|
1 | 20 | 74.3 | 570 | 72.3 | 68 | 65 | |
4 | 23 | 3.8 | 65.3 | 552 | 63.3 | 56 | 53 |
8 | 24.5 | 5.3 | 60.8 | 546.7 | 58.8 | 49.9 | 46.9 |
10 | 25 | 5.9 | 59.3 | 545.4 | 57.3 | 48 | 45 |
16 | 25 | 7.5 | 56.2 | 543 | 54.2 | 43.9 | 40.9 |
20 | 25 | 8.4 | 54.8 | 542.1 | 52.8 | 42 | 39 |
25 | 24.3 | 9.4 | 53.3 | 541.2 | 51.3 | 40 | 37 |
31.25 | 23.6 | 10.5 | 51.9 | 540.4 | 49.9 | 38.1 | 35.1 |
62.5 | 21.5 | 15 | 47.4 | 538.6 | 45.4 | 32.1 | 29.1 |
100 | 20.1 | 19.1 | 44.3 | 537.6 | 42.3 | 28 | 25 |
200 | 18 | 27.6 | 39.8 | 536.5 | 37.8 | 22 | 19 |
250 | 17.3 | 31.1 | 38.3 | 536.3 | 36 | 20 | 17 |
300 | 16.8 | 34.3 | 37.1 | 536.1 | 35.1 | 18.5 | 15.5 |
500 | 15.2 | 45.3 | 33.8 | 535.6 | 31.8 | 14 | 11 |
Part Number | Description | Standard Length |
114-2100Y204X | CAT6A F/UTP 4 Pair External Cable UV-LSZH | 305 mtr |