RIBBON TRUNK CABLE-BLUNT END TYPES

Norden MTP/MPO blunt end type ribbon cable provide an efficient way to install a large number of cables quickly. It also provides high flexibility on unplugging and re-use. Non metalic FRP strength member in the cable give it good tensile strength, Water blocking jelly in the tube and tape over the tube give it excellent water and moisture resistance, Polyester yarns used to bind the cable core. It is especially suitable for the areas that require rapid deployment of high-density backbone cabling in data centers, and high fibre environments for high performance. MTP/MPO Trunk Cables are factory pre-terminated and available with OM3, OM4, OM5 & SM assemblies

Norden MTP/MPO blunt end type ribbon cable provide an efficient way to install a large number of cables quickly. It also provides high flexibility on unplugging and re-use. Non metalic FRP strength member in the cable give it good tensile strength, Water blocking jelly in the tube and tape over the tube give it excellent water and moisture resistance, Polyester yarns used to bind the cable core. It is especially suitable for the areas that require rapid deployment of high-density backbone cabling in data centers, and high fibre environments for high performance. MTP/MPO Trunk Cables are factory pre-terminated and available with OM3, OM4, OM5 & SM assemblies.

STANDARDS

  • EIA/TIA, Telecocordia GR-326-CORE Standards
  • TIA 605-4 (FOCIS 5)
  • IEC61754-7 

FEATURES

  • Easy to deploy - Factory-terminated systems can save installation and network reconfiguration time.
  • Reliability - use high-standard components to ensure product quality.
  • Factory terminated and tested
  • Allow easy migration from 10GbE to 40GbE or 100GbE
  • Ideal for 400G High-Speed Network connection 

MECHANICAL & ENVIRONMENTAL CHARACTERISTICS

Fibre Mode 
Single-mode: OS2 9/125µm
Multimode: OM3/OM4/OM5 50/125µm
Connector
MTP/MPO Standard & MTP/MPO PRO
Connector Type 
Connector A
MTP/MPO
Connector B
Un-Terminated 
Polarity
Type A,Type B,Type C & Universal
Strength Member
FRP
Length
Standard & Custom Lengths
Cable Jacket
PVC, LSZH, OFNP & OFNR
Operating Temperature
-20°C ~ 70°C
Storage Temperature 
-20°C ~ 70°C
Installation Temperature
0°C ~ 50°C

TRUNK CABLE PHYSICAL SPECIFICATIONS – 12F (Flat Type) 

Fiber Count 
Cable Size (mm)
MAX Tensile (N) 
MAX Crush (N/100) 
Minimum Bend Radius (mm) 


InstallationLong Term
12
2.5±0.3(H)x4.6±0.3(W)
24050020D
10D

TRUNK CABLE PHYSICAL SPECIFICATIONS – 144F (Round Type) 

Fiber Count 
Cable Diameter (mm)
MAX Tensile (N) 
MAX Crush (N/100) 
Minimum Bend Radius (mm) 


InstallationLong Term
144
15.8
2700100025D
15D

RIBBON TRUNK CABLE-BLUNT END TYPES

Performance Specifications Multi Mode System (OM3) Multi Mode System (OM4) Multi Mode System (OM5) Single Mode System (OS2)
Maximum Attenuation (dB/km)850 nm1300 nm
850 nm 1300 nm850 nm
1300 nm
850 nm
1300 nm

3.5 
1.53.5 1.53.5 
1.5
3.5 
1.5


MTP / MPO TERMINATION

Type Single-mode (APC polish) Single-mode (PC polish) Multi– mode (PC polish)
Fibre Type
G652D, G657A1, G657A2
G652D, G657A1, G657A2
62.5/125, OM2, OM3, OM4, OM5
Maximum Insertion Loss Elite / Low Loss Standard Elite / Low Loss Standard Elite / Low Loss Standard

≤0.35 dB 0.25 dB Typical ≤0.70 dB 0.5 dB Typical ≤0.35 dB 0.25 dB Typical ≤0.70 dB 0.5 dB Typical ≤0.35 dB 0.2 dB Typical ≤0.7 dB 0.35 dB Typical
Return Loss ≥60 dB ≥50 dB ≥30 dB
Durability
≥200 times
≥200 times
≥200 times
Test Wavelength
1310 nm / 1550 nm
1310 nm / 1550 nm
850 nm / 1300 nm