Category 6 U/UTP 24AWG 4 Pair Stranded Cable

Category 6 U/UTP 24AWG 4 Pair Stranded Cable

Norden Category 6 UTP stranded cables exceed Category 6 / Class E specification. It is tested to 250 MHz frequency range and designed to support Gigabit 1000Base-T and 1000Base-Tx applications upto 100m. Norden Category 6 UTP cables are having standard packing in 305m easy pull out boxes. Extremely high pair-balance providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation, maximizing noise immunity and providing high alien cross talk performance to UTP (Unshielded Twisted Pair) cabling systems.

Norden Category 6 UTP stranded cables exceed Category 6 / Class E specification. It is tested to 250 MHz frequency range and designed to support Gigabit 1000Base-T and 1000Base-Tx applications upto 100m. Norden Category 6 UTP cables are having standard packing in 305m easy pull out boxes.
Extremely high pair-balance providing excellent EMC (Electro Magnetic Compatibility), minimizing radiation, maximizing noise immunity and providing high alien cross talk performance to UTP (Unshielded Twisted Pair) cabling systems.



MATERIAL CONSTRUCTION & DESIGN

Conductor Material Bare Copper
Conductor Size 7/0.20 mm, 24 AWG
Conductor Construction Stranded
Insulation Material High Density PE
Insulation Diameter 0.88±0.05 mm
Conductor Unit Identification Solid/Stripe
Colour Code Per TIA/EIA 568-B
Total Number of Wires 8
Seperator Yes
Outer Jacket LSZH or PVC
Outer Jacket Thickness & Ex. Diameter 0.50 mm, 6.0±0.20 mm
Outer Jacket Colour Per Requirement
Marking Per Requirement

ELECTRICAL & MECHANICAL CHARACTERISTICS

Frequency Range 1-250 MHz
Impedance 100 ±15 Ω
Coupling Attenuation 40 dB min @ 30-100 MHz 40-20 Log (f/100) @100-300 MHz
DC Resistance 73 Ω/km norm.
Max.Resistance Unbalance 2.5 %
Capacitance 5.6 nF/100m Max
Capacitance Unbalance 3.3 pF/m max
Propagation Delay Skew 35 ns/100m max
Velocity of Propagation 69 %
Dielectric Strength 1 KV/Minute
Min. Insulation Resistance 5 GΩ•km
Dielectric Strength 1 KV/Minute
Max.Tensile Strength - Short Term 110 N
Min. Bend Radius 53.6 mm
Operating Temperature Range -10 °C +65 °C

TRANSMISSION PERFORMANCE

Cat. 6 Un-screened Pair Horizontal Cables*
Freq.
MHz
Attenuation
dB/100m @ 20ºC
NEXT
dB
PSNEXT
dB
RL
dB
ACR-N
dB
PS ACR-N
dB
1 3.0 65.0 62.0 19.0 62.0 59.0
4 4.0 63.0 60.5 19.0 59.0 56.5
10 6.3 56.6 54.0 19.0 50.2 47.7
20 9.0 51.6 49.0 17.5 42.6 39.9
31.25 11.4 48.4 45.7 16.5 37.0 34.3
100 21.3 39.9 37.1 12.0 18.6 15.8
200 31.5 34.8 31.9 9.0 3.3 0.3
250 35.9 33.1 30.2 8.0 -2.8 -5.8
Part Number Description Standard Length
119-10001104X Category 6 U/UTP 24AWG 4 Pair Stranded Cable PVC 305 mtr
119-10002104X Category 6 U/UTP 24AWG 4 Pair Stranded Cable LSOH 305 mtr

X: BK(Black), BL(Blue), GN(Green), GY(Gray), RD(Red), WH(White), YL(Yellow)