The Unshielded power limited fire protective cable from NORDEN is suitable to be used for fire limited fire protective , control and instrumentation purposes. The cable is constructed with XLPE insulation and PVC outer jacket.
The Unshielded power limited fire protective cable from NORDEN is suitable to be used for fire limited fire protective , control and instrumentation purposes. The cable is constructed with XLPE insulation and PVC outer jacket.
CABLE CONSTRUCTION
Characteristic | Value |
No. of Conductor | 2 |
Conductor Size | 16 AWG ,7*0.49 mm |
Insulation Diameter | 2.35 ± 0.05 mm |
Jacket Thickness | 1.35 mm |
Jacket Diameter | 7.7 ± 0.3 mm |
Min. Bending Radius (Install) | 10 X D |
Operating Temperature | -20°C To +90°C |
Characteristic | Value | Unit |
Nom Conductor DCR | Ω/km | 14.9 |
Dielectric Strength between Pairs | KV/min | 1.5 |
Max. Operating Voltage UL | V/min | 600V |
Test Material | PVC |
Before Tensile Strength (Mpa) | ≥ 13.8 |
Aging Elongation (%) | ≥ 100 |
After Tensile Strength (Mpa) | ≥ 85 |
Aging Elongation (%) | ≥ 100 |
Cold Bend (-20±°C x 4 hrs) | No Crack |
PART NUMBER | DESCRIPTION |
75-X102161 | 2 Core 16 AWG Power Protective Unshielded Tray Cable PVC |