Fire Resistant Cable PH 120 SFR Insulation

NORDEN Fire Resistant Cable PH 120 SFR Insulation cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, hotels etc. FireNor products_backup have low smoke density, are halogen free and they don't emit poisonous gases.

NORDEN Fire Resistant Cable PH 120 SFR Insulation cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, hotels etc. FireNor products_backup have low smoke density, are halogen free and they don't emit poisonous gases.

CABLE CONSTRUCTION

Conductor

Solid Bare Copper
IEC 60228 class 1

Screen

Aluminium Laminated Polyester Tape

Sheath

HFFR EN 50290-2,BS 7655 LTS1/LTS3
VDE 0207

Insulation

Fire resistant silicon rubber
(HD 22.1, BS 7655 EI2)

Separator

Polyester Type

Sheath Color

Red (RAL 3000) or White

Insulation Colour

2 Core: Blue/Brown

Earth Wire

Tinned Copper to IEC 60228

Standard Packing Mode

100 mtr / Plywood Reel
500 mtr / Plywood Reel (optional)




Flame Tests Insulation Integrity Smoke Density Corrosive Gases Measurement Other Stanaderds

IEC 60332-1
IEC 60332-3-24
EN 50266-2-4

IEC 60331
BS 6387 C, W, Z
Cat,C fire @950°C - 180 min
Cat,W fire and water @ 650°C
-15 +15 min
Cat,Z fire and mechanical
shocks @ 950°C - 15 min.
EN 50200 PH 120
EN 50200(Annex E)

IEC 61034
EN 50268
HD 606

IEC 60754-2
EN 50267

BS 7629-1: 2008
BS 8519 (Clause 11)
BS 5266-1 (Clause 8.2.2a) BS 8539-6 (Clause 16.2)
BS 5839-8 (Clause 27.6) BS 5839-1:2013
(Clause 26.2d Standard)


ELECTRICAL & MECHANICAL CHARACTERISTICS


Properties Value
1.5 mm² 2.5 mm²4.0 mm²

Max. Conductor Resistant @ 20ºC

12.0Ω/km

7.4 Ω/km

4.5 Ω/km 

Min. Insulation Resistant @ 20ºC

200 MΩ/km

Operating Voltage

300/500 V

Test Voltage

2000 V

Temperature Range (Fixed)

-30ºC to + 90ºC

Temperature Range (Flexing)

-5ºC to + 60ºC

Min. Bend Radius (Fixed)

8 x D

Min. Bend Radius (Flexing)

15 x D


PHYSICAL INFORMATION


Nom. Cond.
Cross-Sect. mm²
Conductor Size
no./mm
Earth Wire Size
no./mm
Cable Diameter
mm (±5 %)
Weight Kg/km

2 x 1.5

1/1.37

1/1.37

8.00

98.0

2 x 2.5

1/1.75

1/1.75

9.70

148.0
Part Number Description

55-1502X

Fire Resistant Cable PH120 SFR Insulation, 2C x 1.5mm²

55-2502X

Fire Resistant Cable PH120 SFR Insulation, 2C x 2.5 mm²

55-4003X
Fire Resistant Cable PH120 SFR Insulation, 3C x 4 mm²

X > RD:Red WH:White OR:Orange