NORDEN FireNor PH 120 re resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semiintelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, hotels etc. FireNor products have low smoke density, are halogen free and they don't emit poisonous gases.
NORDEN FireNor PH 120 re resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semiintelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres, schools, shopping centers, airports, factories, hotels etc. FireNor products have low smoke density, are halogen free and they don't emit poisonous gases.
Flame Tests | Circuit Integrity | Smoke Density | Corrosive Gases Measurement | Other Stanaderds |
IEC 60332-1 | IEC 60331-21
(UL 2196 (2hRS)) | IEC 61034-1/2 | IEC 60754-1/2 | NFPA 70,72 & 101 IEC 60228 |
Properties | Value | ||
1.5 mm² | 2.5 mm² | 3.3 mm² | |
Max. Conductor Resistant @ 20ºC | 12.1Ω /km | 7.41Ω/ km | 5.31Ω/ km |
Min. Insulation Resistant @ 0ºC | 200 MΩxkm | ||
Operating Voltage | 300/500 V | ||
Test Voltage | 2000 V | ||
Temperature Rating(Fixed) | -30ºC to + 90ºC | ||
Temperature Rating(Flexing) | -10ºC to + 90ºC | ||
Min. Bend Radius(Fixed) | 8 x D | ||
Min. Bend Radius(Flexing) | 15 x D |
Nom. Cond. Cross-Sect. mm² | Cable Diameter
mm (±5 %) | Weight Kg/100m |
2 x 1.5 | 8.6 ± 0.2mm | 9.00 |
2 x 3.3 | 11.0mm | 15.8 |
3 x 1.5 | 9.2 ± 0.2mm | 12.00 |
4 x 1.5 | 10.5 ± 0.2mm | 16.00 |
2 x 2.5 | 10.4 ± 0.2mm | 13.50 |
3 x 2.5 | 11.3 ± 0.2mm | 18.00 |
Part Number | Description |
5V-1502X | PH120 Stranded Conductor Shielded Fire Resistant Cable, 2C x 1.5mm² |
5V-1503X | PH120 Stranded Conductor Shielded Fire Resistant Cable, 3C x 1.5mm² |
5V-1504X | PH120 Stranded Conductor Shielded Fire Resistant Cable, 4C x 1.5mm² |
5V-2502X | PH120 Stranded Conductor Shielded Fire Resistant Cable, 2C x 2.5mm² |
5V-2503X | PH120 Stranded Conductor Shielded Fire Resistant Cable, 3C x 2.5mm² |
5V-3302X | PH120 Stranded Conductor Shielded Fire Resistant Cable, 2C x 3.3mm² |
X > OR:Orange, RD: Red