OPGW CABLES

Optical Ground Wire (OPGW) features a central aluminium-clad stainless steel tube with aluminium-clad steel (ACS) and aluminium-alloy (AA) wire layers. It serves as both a grounding conductor and a fiber-optic communication medium, ensuring fast, reliable, and cost-effective data, voice, and video transmission while protecting power infrastructure. The optical fibres are enclosed in a central aluminium-clad stainless steel tube, surrounded by a layer of ACS wire and a layer of AA wire. This construction enhances mechanical strength, conductivity, and corrosion resistance. The cable offers high tensile strength, excellent crush resistance, and long-span capability, while its lightweight design reduces the load on transmission towers. Ideal for high-voltage transmission networks, this OPGW solution provides durability, stability, and superior performance in challenging environments.

Optical Ground Wire (OPGW) features a central aluminium-clad stainless steel tube with aluminium-clad steel (ACS) and aluminium-alloy (AA) wire layers. It serves as both a grounding conductor and a fiber-optic communication medium, ensuring fast, reliable, and cost-effective data, voice, and video transmission while protecting power infrastructure. The optical fibres are enclosed in a central aluminium-clad stainless steel tube, surrounded by a layer of ACS wire and a layer of AA wire. This construction enhances mechanical strength, conductivity, and corrosion resistance. The cable offers high tensile strength, excellent crush resistance, and long-span capability, while its lightweight design reduces the load on transmission towers. Ideal for high-voltage transmission networks, this OPGW solution provides durability, stability, and superior performance in challenging environments.


CONSTRUCTION & DESIGN

AL- Clad Stainless Steel Tube Diameter

6 mm (Stainless Steel Tube Diameter: 3.5 mm)

No.of Al-Clad Steel Tube

1
AL-Clad Steel Tube Conductivity
61.0%
AL- Clad Steel Wire Diameter
3 mm
No.of AL-Clad Steel Wires
AL-Clad Steel Wire Conductivity
20.3%
AL Alloy Wire Diameter
3 mm
No.of AL Alloy Wires
15
AL Alloy Wires Conductivity 52.5%
Carrying Area / Cross Section
187.2 mm2
Section of AL- Clad Stainless Steel Tube
17.5  mm2
Section of AL-Clad Steel Wire
63.6 mm2
Section of AL Alloy Wire
106 mm2
Outer Layer DirectionRight Hand 


MECHANICAL & ENVIRONMENTAL CHARACTERISTICS

Ultimate Tensile Strength
122.33 kN
Rated Tensile Strength
112.55 kN
Elasticity Coefficient
98.0 kN/mm2
Thermal Expansion Coefficient
17.4 x 10-6 /℃
Everyday Tension - EDS ( 20% RTS)
23 kN
Max. Allowable Tension - MAT ( 40% RTS)
45 kN
D.C. Resistance at 20℃
0.220 Ω/Km
Short-Circuit Current (1s, 20℃~200℃)
18.1 kA
Short-Circuit Current Capacity (20℃~200℃)
328.8 kA2·s
Min. Bending Radius (Dynamic)
360 mm
Installation Temperature Range
-10℃ to +50℃
Operating Temperature Range-40℃ to +80℃ 
Transportation Temperature Range-40℃ to +80℃ 
Part NumberFibre CountOuter
Diameter
(mm)
Weight
(N.W Kg )
4045-11048FXXCL
48
18.0 
789