Standard Fire Resistant Cable PH120

Standard Fire Resistant Cable PH120

NORDEN FireNor Standard fire resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres,schools, shopping centers, airports, factories, hotels etc.FireNor products have low smoke density, are halogen free and they don't emit poisonous gases.

NORDEN FireNor Standard fire resistant cables are manufactured within the specific requirement of fire resistant cable standards. The fire resistant cable assures reliable circuit integrity to keep emergency evacuation systems operational even whilst the cable is burning. FireNor fire resistant cables can be used for fire alarm systems, power supply or control of equipment that needs to function during a fire such as warning, emergency lighting, evacuation and monitor systems. The place of usage is intelligent or semi-intelligent buildings where dense human population or valuable goods are found. These can be hospitals, cinemas, theatres,schools, shopping centers, airports, factories, hotels etc.FireNor products have low smoke density, are halogen free and they don't emit poisonous gases.

CABLE CONSTRUCTION

Conductor

EN 60228 Class 1 (RE)

Electrolytic Copper

Drain Wire

Tinned Copper

Sheath

HFFR Compound

EN 50290-2-27

Insulation

EN 50363-1 EI2 Cross-linked

Ceramic Forming Polymer Compound

Wrapping

Polyester Tape

Sheath Color

Red(RAL 3000)

Insulation Color

Blue, Brown, Black, Grey
 

Overall Screen

Aluminium Polyester Tape

 

Standard Packing Mode

100 mtr / Plywood Reel

500 mtr / Plywood Reel (optional)


Flame Tests Insulation Integrity Smoke Density Corrosive Gases & Halogen Free Test

IEC 60332-1-2
VDE 0482-332-1-2
EN 60332-1-2
IEC 60332-3-24
VDE 0482-332-3-24
EN 60332-3-24

IEC 60331-23
BS 6387 C, W, Z
Cat,C fire @950°C - 180 min
Cat,W fire and water @ 650°C
-15 +15 min
Cat,Z fire and mechanical
shocks @ 950°C - 15 min.
EN 50200 PH 120

IEC 61034-2
VDE 0482-1034-2
EN 61034-2

IEC 60754-2
VDE 0482-267-2-3
EN 50267-2-3
IEC 60754-1
VDE 0482-267-2-1
EN 50267-2-1

ELECTRICAL & MECHANICAL CHARACTERISTICS

Properties Value
1.0 mm² 1.5 mm² 2.5 mm²

Max. Conductor Resistant @ 20ºC

18.1ohm/km

12.1 ohm/km

7.4 ohm /km

Min. Insulation Resistant @ 0ºC

200 Mohm xkm

Operating Voltage

300/500 V

Test Voltage

2000 V

Temperature Rating(Fixed)

-30ºC to + 70ºC

Temperature Rating(Flexing)

-5ºC to + 60ºC

Min. Bend Radius(Fixed)

6 x D

Min. Bend Radius(Flexing)

15 x D

PHYSICAL INFORMATION

Nom. Cond.
Cross-Sect. mm²
Conductor Size
no./mm
Drain Wire Size no./mm Cable Diameter
mm (±5 %)
Weight Kg/km

2 x 1.0

1/1.12

1/1.12

6.0

60.0

2 x 1.5

1/1.37

1/1.37

7.0

79.0

3 x 1.5

1/1.37

1/1.37

7.6

105.0

4 x 1.5

1/1.37

1/1.37

8.3

128.0

2 x 2.5

1/1.75

1/1.75

8.4

113.0

3 x 2.5

1/1.75

1/1.75

9.0

153.0

4 x 2.5

1/1.75

1/1.75

10.10

195.0


Part Number Description

5A-1002XY

Standard Fire Resistant Cable EN 50200 PH120, 2C x 1.0mm²

5A-1502XY

Standard Fire Resistant Cable EN 50200 PH120, 2C x 1.5mm²

5A-1503XY

Standard Fire Resistant Cable EN 50200 PH120, 3C x 1.5mm²

5A-1504XY

Standard Fire Resistant Cable EN 50200 PH120, 4C x 1.5mm²

5A-2502XY

Standard Fire Resistant Cable EN 50200 PH120, 2C x 2.5mm²

5A-2503XY

Standard Fire Resistant Cable EN 50200 PH120, 3C x 2.5mm²

5A-2504XY

Standard Fire Resistant Cable EN 50200 PH120, 4C x 2.5mm²

X(Color Code) > BK:Black, RD:Red, 

Y(Packing Length) > 1:100mtr, 2: 500mtr