6/10kVA Online Transformerless Rack Mount UPS

The Max Power Pro Series 6 and 10 kVA Rack Mount Uninterruptible Power Supply (UPS) systems are designed to provide robust and reliable power protection for critical equipment in demanding environments. These UPS systems are engineered to handle various applications, including data centers, telecommunication facilities, industrial operations, and commercial buildings. With their unique capability of accepting a 3-phase input and providing a single-phase output, they offer versatility and efficiency for various power needs.

The Max Power Pro Series 6 and 10 kVA Rack Mount Uninterruptible Power Supply (UPS) systems are designed to provide robust and reliable power protection for critical equipment in demanding environments. These UPS systems are engineered to handle various applications, including data centers, telecommunication facilities, industrial operations, and commercial buildings. With their unique capability of accepting a 3-phase input and providing a single-phase output, they offer versatility and efficiency for various power needs. 

 GENERAL FEATURES

  • Online double conversion with DSP control
  • Generator compatible
  • ECO mode operation for energy saving
  • LCD supports Rack/Tower convertible design
  • Intelligent fan speed regulation
  • Dual input source
  • Input current harmonic:<3%
  • Support 3/1 and 1/1 operation
  • N+X parallel redundancy, support maximum 4 units in parallel
  • Self-testing when UPS startup
  • 50/60Hz Frequency converter mode
  • Cold Start
  • Wide input voltage range: 208~478Vac
  • Wide input frequency range: 40~70Hz
  •  Optimization battery group, the quantity of battery: 16/18/20pcs (32~40pcs supportable)
  • Multiple communication interface: RS232/RS485/ EPO/(Relay card/SNMP card optional)


      ModelCN53106MP-RM
      CN53110MP-RM

      Capacity

      kVA

      6

      10

      kW

      6

      10

      Input

      Normal Voltage

      380/400/415Vac (3PH+N+PE) / 220/230/240Vac (L+N+PE)

      Operating Voltage Range

      208~478Vac; 120~270Vac


      Operating Frequency Range

      40~70Hz (50/60Hz Auto-Sensing) 


      Power Factor

      ≥0.99 


      Bypass voltage range

      Max.voltage: 220V: +25% (Optional +10%, +15%, +20%)

      230V: +20% (Optional +10%, +15%)

      240V: +15% (Optional +10%)

      Min.voltage: -45% (Optional -10%, -20%, -30%) 


      Frequency 
      Frequency protection range
      (50/60±0.1%)Hz

      Output

      Output voltage

      220/230/240Vac (L+N+PE)hh

      Voltage regulation
      ±1%

      Power factor
      1.0

      Output Frequency

      Line mode

      ±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional)

      Bat. mode

      (50/60±0.1%)Hz


      Transfer Time

      AC mode to Bat.mode

      0ms

      Inverter to Bypass

      0ms


      Output waveform

      Pure Sinewave


      Crest factor
      3:1

      Harmonic distortion (THDv)

      ≤2% with linear load, ≤5% with non-linear load


                                                        AC mode
      Load≤110%: last 60min; ≤125%: last 10min; ≤150%: last 1min; ≥150%: turn to bypass mode immediately

      Overload                                  Bat.mode
      Load≤110%: last 10min; ≤125%: last 1min; ≤150%: last 5s; ≥150%: shut down UPS immediately 

                                                      Bypass mode Breaker (Load<125%, long-term operation)

      Efficiency 
      Efficiency
      Up to 93.5% 

      Battery

      Battery voltage

      ±96/±108/±120Vdc (16/18/20pcs optional);

      (16pcs default, 20pcs no power derating; 18pcs output power factor 0.9; 16pcs output power factor 0.8;)

      ±192/204/216/228/240Vdc (32/34/36/38/40pcs supportable)  


      Charging current

      12A (Max.)

      14A (Max.) 

      Physical 

      Dimension W×D×H (mm)

      443×580×131 (3U)

      Net weight (kg)

      27

      28

      Environment

      Operating temperature

      0~40°C 

      Storage temperature

      -25~55°C


      Humidity range

      0~95% (Non-condensing)


      Altitude

      <1500m, derating required when >1500m


      Noise level

      <53dB at 1 Meter

      <55dB at 1 Meter

      Standards

      Safety

      IEC/EN 62040-1, IEC/EN 62477-1

      EMC

      IEC/EN 62040-2 (IEC 61000-4-2, IEC 61000-4-3, IEC 61000-4-4, IEC 61000-4-5, IEC 61000-4-6, IEC 61000-4-8, 

      IEC 61000-4-11, IEC 61000-2-2


       

       EXTERNAL BATTERY PACK

          MODELCNBC20240CR
          CNBC40240CR
          BATTERY SYSTEM

          Battery type
          VRLA (Valve Regulated Lead Acid Battery - SMF)
          Typical battery recharging time 
          6~8 hours (to 90% of full capacity) 

          Typical battery life
          3~5 years, depend on discharging cycle and ambient temperature

          System voltage 
          240Vdc

          Battery quantity 
          1x20 Pcs
          2x20 Pcs
          Capacity
          9Ah/12V

          PHYSICAL

          Dimension W x D x H (mm)
          443×720×131 (3U) 
          482×861.5×175 (4U) 
          Net weight (kg)
          58/63
          138/154
          ENVIRONMENT


          Operating environment
          0°C~40°C

          Relative humidity 
          0~95% (Non condensing) 

          Noise level 
          <40dB at 1 Meter

           

          Part NumberDescription

          CN53106MP-RM

          6kVA Double Conversion Transformer-less Rack Mount UPS (External Battery)

          CN53110MP-RM

          10kVA Double Conversion Transformer-less Rack Mount UPS (External Battery)
          CNBC20240CR
          240VDC Rack Mount Battery Pack
          CNBC40240CR
          240VDC Rack Mount Battery Pack

          COMPATIBLE ACCESSORIES

          Part NumberDescription
          CNS01
          SNMP Card
          CNRM1020RRack Mounting Rail Kit for 10-20kVA RM UPS
          CNRM240BPRBattery Pack Rack Mounting Rail Kit