Norden's Maxpower Series 1 kVA UPS is an online double conversion UPS that features a single phase in both input and output, and an output power factor of 0.9. This tower-type UPS is designed to be used in commercial buildings and offices, and can be connected to desktops and servers.
Norden's Maxpower Series 1 kVA UPS is an online double conversion UPS that features a single phase in both input and output, and an output power factor of 0.9. This tower-type UPS is designed to be used in commercial buildings and offices, and can be connected to desktops and servers.
Model | CN7001MPI-RM/CN7001MPE-RM | ||
Capacity | VA | 1000 | |
Watts | 900 | ||
Phase | Single phase with ground | ||
Input | Normal Voltage | 208/220/230/240Vac | |
Input Voltage Range | 110~300Vac (176~264Vac @ 100% load) | ||
Frequency Range | 40~70Hz(50/60Hz Auto Sensing | ||
Power Factor | ≥0.99 @Nominal voltage(100% load) | ||
Output | Output Voltage | 208/220/230/240Vac | |
Power Factor | 0.9 | ||
Voltage Regulation | ±1% | ||
Frequency range (Synchronized range) | 46~54Hz/56~64Hz | ||
Frequency range (Batt.mode) | 50Hz/60Hz±0.1Hz | ||
Current crest ratio | 3:1 | ||
Harmonic Distortion (THDv) | ≤3% THD(Linear load) | ||
≤5% THD(Non-linear load) | |||
Transfer Time | AC to DC | Zero | |
Inverter to Bypass | 4ms(Typical) | ||
Waveform | Pure Sinewave | ||
Efficiency | AC Mode | 89% | |
Battery Mode | 85% | ||
Battery | Internal | Battery Type | 12V/9AH |
Numbers | 3 | ||
Typical recharging time | 4 hours recover to 90% capacity | ||
Charging current(max.) | 1A | ||
Charging Voltage | 41.1Vdc ±1% | ||
Battery | External | Battery Number | 3 |
Charging voltage | 41.1Vdc ±1% | ||
Charging Current | 12A | ||
Indicators | LCD | Load level, Battery level, AC mode, Battery mode, Bypass mode and Fault indicators | |
Alarm | Battery Mode | Beeping every 4 seconds | |
Battery Low | Beeps every second | ||
Overload | Beeps twice per second | ||
Fault | Continously beeping | ||
Physical | Dimension W x D x H (mm) | Standard model | 440 x 460 x 86.5 (2U) |
Long run model | 440 x 325x 86.5 (2U) | ||
Net weight (kg) | Standard model | 11.3/14 | |
Long run model | 5.6 | ||
Environment | Humidity | 20-90% RH @ 0-40°C (Non-condensing) | |
Noise level | <50dB @ 1 Meter | ||
Management | Smart RS232/USB | Supports Windows® 2000/2003/XP/Vista/2008 Windows® 7/8 Linux, FreeBSD and MAC | |
Optional SNMP | Power management from SNMP manager and web browser | ||
Standards | Safety | IEC/EN62040-1,IEC/EN62477-1 | |
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8,IEC61000-4-11,IEC61000-2-2 |
EXTERNAL BATTERY PACK | ||
Model | CNBC00124CR | CNBC00136CR |
BATTERY SYSTEM | ||
Battery Type | VRLA (Valve Regulated Lead Acid Battery - SMF) | |
Typical battery recharging time | 6~8 hours (to 90% of full capacity) | |
Typical Battery Life | 3~5 years, depend on discharging cycle and ambient temperature | |
System voltage | 36Vdc | |
Battery quantity | 6 | |
Capacity | 9Ah/12V (7Ah/12V optional | |
PHYSICAL | ||
Dimension W x D x H (mm) | 440 x 430 x 86.5 | |
Net weight(kg) | 22.5 | |
ENVIRONMENT | ||
Operating environment | 0°C~40°C | |
Relative humidity | 0~95% (Non condensing) | |
Noise Level | <40dB at 1 Meter |
Part Number | Description | ||
CN7001MPI-RM | 1kVA Online Transformerless Rack Mount UPS (Internal battery) | ||
CN7001MPE-RM | 1kVA Online Transformerless Rack Mount UPS (External battery) | ||
CNBC00124CR | 24VDC Rack Mount Battery Pack | ||
CNBC00136CR | 36VDC Rack Mount Battery Pack |
Part Number | Description | ||
CNRM0110R | Rack Mounting Rail Kit for 1-10kVA RM UPS | ||
CNRM0110BPR | Battery Pack Rack Mounting Rail Kit for 1-10kVA RM UPS | ||
CNS02 | Mini SNMP Card |