15kVA Double Conversion Transformer-less Rack Mount UPS

Norden's Maxpower Pro Series 15 kVA UPS is an online double conversion UPS that features 3/3, 3/1 operation and a unity output power factor. This model features a convertible rack-tower design and parallel redundancy capabilities, making it ideal for data center applications.

Norden's Maxpower Pro Series 15 kVA UPS is an online double conversion UPS that features 3/3, 3/1 operation and a unity output power factor. This model features a convertible rack-tower design and parallel redundancy capabilities, making it ideal for data center applications.

 GENERAL FEATURES

  • LCD support Rack/Tower convertible design
  • N+X parallel redundancy, support maximum  4 units in parallel 
  • Online double conversion with full digital control
  • Wide input frequency range 40~70Hz 
  • Wide input voltage range:208~478Vac
  • Input current harmonic:<3%
  • Maximum Charging current up to 20A(Settable) 
  • Dual Input Sources
  • ECO mode operation for energy saving
  • Support 3/3 and 3/1 and 1/1 operation 
  • Generator compatible
  • Cold Start
  • Self-testing when UPS start-up
  • 50/60Hz Frequency converter mode
  •  Intelligent fan speed regulation 
  • The quantity of battery:30-50pcs is settable

      ModelCN5315MP-RM

      Capacity

      kVA

      15kVA

      Watts

      15000

      Input

      Normal Voltage

      380/400/415Vac (3Ph+N+PE) 220/230/240Vac (L+N+PE)

      Operating Voltage Range

      208~478Vac

      Operating Frequency Range

      40~70Hz (50/60Hz Auto-Sensing)

      Power Factor

      ≥0.99 

      Bypass voltage range

      Max.voltage:220V:+25% (Optional+10%,+15%,+20%) 240V:+15% (Optional+10%) Min.voltage:-45% (Optional-20%,-30%), 230V:+20% (Optional+10%,+15%) 

      ECO range

      Same as the bypass

      Generator input

      Support

      Output

      Rated voltage

      380/400/415Vac (3Ph+N+PE) 220/230/240Vac (L+N+PE)

      Power factor

      1

      Voltage Regulation

      ±1%

      Frequency

      Line mode

      ±1%/±2%/±4%/±5%/±10% of the rated frequency (Optional)

      Bat. mode

      50/60(±0.1)Hz

      Crest Factor

      3:1

      Harmonic Distortion (THDv)

      ≤2% with linear load, ≤5% with non-linear load

      Efficiency

      94.5%

      Output Waveform
      Pure Sine Wave

      Battery

      Battery Numbers

      30/32/34/36/38/40/42/44/46/48/50pcs with Neutral

      Charging current

      18A Max.(charge current can be set according to battery capacity installed)

      System
      Features

      Transfer time

      Mains to battery:0ms; Inverter to bypass:0ms

      Overload

      Line mode

      Load≤110%: last 60min, ≤125%: last 10min, ≤150%: last 1min, ≥150% turn to bypass mode immediately

      Bypass mode

      Breaker ( Load < 125%, long-term operation)

      Short circuit

      Hold whole system

      Overheat

      Line mode: Turn to bypass; Backup mode: shut down UPS immediately

      Battery low

      Alarm and switch off

      Self-diagnostics

      Upon power on and software control

      Battery

      Advanced battery management

      Audible & Visual alarms

      Line failure, Battery under voltage, Overload, System fault

      LED & LCD display

      Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault 

      LCD display

      Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage, Inner temperature & Remaining battery backup time

      Communication interface

      RS232, RS485, Parallel, Intelligent Slot(SNMP card/ Relaycard (Optional)),BMS (Optional),EPO port Output port, MAINTAIN-AUXSWS port

      Environment

      Operating temperature

      0~40°C 

      Storage temperature

      -25~55°C

      Humidity range

      0~95% (Non-condensing)

      Altitude

      <1500m

      Noise level

      <55dB 

      IP Rating 
      IP 20

      Standards

      Safety

      CE; IEC/EN62040-1,IEC/EN62477-1

      EMC

      IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

      Physical

      Dimension WxDxH(mm)

      443 x 580 x 131            

      Net Weight (kg)

      31

       

       EXTERNAL BATTERY PACK

      MODELCNBN40480CR
      BATTERY SYSTEM

      Battery type

      VRLA (Valve Regulated Lead Acid Battery - SMF)

      Typical battery recharging time6~8 hours (to 90% of full capacity) 
      Typical battery life3~5 years, depend on discharging cycle and ambient temperature 
      System voltage 
      480Vdc
      Battery quantity
      40Pcs
      Capacity
      9Ah/12V
      PHYSICAL
      Dimension W x D x H (mm) 
      443x861.5x175
      Net weight (kg)
      114/123
      ENVIRONMENT

      Operating environment
      0°C~40°C
      Relative humidity 
      0~95% (Non condensing) 
      Noise level 
      <40dB at 1 Meter
                                         
      Part NumberDescription

      CN5315MP-RM

      15kVA Double Conversion Transformer-less Rack Mount UPS (External Battery)

      CNBN40480CR
      480VDC Rack Mount Battery Pack

      COMPATIBLE ACCESSORIES

      Part NumberDescription
      CNS01
      SNMP Card
      CNRM1020R
      Rack Mounting Rail Kit for 6-20kVA RM UP
      CNRM240BPR
      Battery Pack Rack Mounting Rail Kit