6kVA Online Transformer-less Rack Mount UPS

Maxpower RM Series is a small to medium power transformer-less UPS of CellNor. This series is the classic product of CellNor. It releases very early and designs with high standard; This series is improved continually combined with customers’ application feedback, and it became a very cost-effective product series. This product series has a very good sale performance , and received highly praises from customers. The categories of this UPS are abundant, and the product is stable and reliable, it can meet the demands of small to medium power UPS of customers.

Maxpower RM Series is a small to medium power transformer-less UPS of CellNor. This series is the classic product of
CellNor. It releases very early and designs with high standard; This series is improved continually combined with customers’
application feedback, and it became a very cost-effective product series. This product series has a very good sale
performance , and received highly praises from customers. The categories of this UPS are abundant, and the product is
stable and reliable, it can meet the demands of small to medium power UPS of customers.

 GENERAL FEATURES

  • High power density

  • Rack/Tower convertible design

  • N+X parallel redundancy support maximum 4 unit in parallel

  • Online double conversion with full digital control

  • Wide input voltage range:110~286Vac

  • Wide input frequency range

  • Generator compatible

  • ECO mode operation for energy saving

  • Self-testing when UPS start-up

  • Maximum charging current up to 10A

  • Cold start

  • Intelligent fan speed regulation

Model CN7006MP-RM

Capacity

VA

6000

Watts

5400

Input

Normal Voltage

220/230/240Vac(L+N+PE) 

Operating Voltage Range

110~286Vac

Operating Frequency Range

40~70Hz (50/60Hz Auto-Sensing)

Power Factor

≥0.99 

Bypass voltage range

Max. voltage: 220V: +25%(optional +10%,+15%,+20% )
230V: +20% (optional +10%, +15%)
240V: +15% (optional +10%)
Min. voltage: -45% (optional -20%, -30%)

Bypass frequency range 
Frequency protection range:±10%

ECO range

Same as the bypass

Harmonic distortion (THDi)

≤2% with linear load, ≤5% with non-linear load

Generator input

Support

Output

Output voltage

220/230/240Vac

Power factor

0.9

Voltage Regulation

±1%

Frequency

Line mode

±1%/±2%/±4%/±5%/±10% of the rated frequency(optional)

Bat. mode

50/60(±0.1)Hz

Crest Factor

3:1

Harmonic Distortion (THDv)

≤2% with linear load, ≤5% with non-linear load

Efficiency

>94%

Battery

Battery voltage

192/216/240Vdc (16/18/20pcs)

Backup time

Depends on the capacity of external batteries Estimated remaining time displayed on the LCD

Typical recharging time

6~8 hours (to 90% of full capacity)

Charging current

Maximum current 10A; charging current can be set according to battery capacity installed.

System
Features

Transfer time

Mains to battery:0ms; Inverter to bypass:0ms 

Overload

Line mode

Load≤110%:60min; ≤125%:last 10min; ≤150%:last 1min;>150% turn to bypass mode

Bypass mode

40A(Input breaker)

Short circuit

Hold whole system

Overheat

Line mode: Turn to bypass; Backup mode: shut down UPS immediately

Battery low

Alarm and switch off

Self-diagnostics

Upon power on and software control

Battery

Advanced battery management

Audible & Visual alarms

Line failure, Battery under voltage, Overload, System fault

LED & LCD display

Line mode, Bat. mode, Eco mode, Bypass mode, Battery under voltage, Overload & UPS Fault

LCD display

Input voltage, Input frequency, Output voltage, Output frequency, Load percentage, Battery voltage,
Inner temperature & Remaining battery backup time

Communication interface

RS232,USB,SNMP card(optional), Relay card (optional)

Environment

Operating temperature

0~40°C 

Storage temperature

-25~55°C

Humidity range

20~95% (Non-condensing)

Altitude

<1500m

Noise level

<55dB at 1Meter

Physical

Dimension

440 x 625 x 86.5

Weight

16

Standards

Safety

IEC/EN62040-1,IEC/EN62477-1

EMC

IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8

IEC61000-4-11,IEC61000-2-2

 

 EXTERNAL BATTERY PACK


MODELCNBC06120CR
BATTERY SYSTEM

Battery type

VRLA (Valve Regulated Lead Acid Battery - SMF)

Typical battery recharging time 

6~8 hours (to 90% of full capacity) 

Typical battery life
3~5 years, depend on discharging cycle and ambient temperature
System voltage 
240Vdc
Battery quantity
20 PCS
Capacity
9Ah/12V
PHYSICAL
Dimension W x D x H (mm) 
440 x 680 x 131 
Net weight (kg)
58/63
ENVIRONMENT

Operating environment
0°C~40°C
Relative humidity 
0~95% (Non condensing) 
Noise level 
<40dB at 1 Meter
                                   
Part Number Description

CN7006MP-RM

6kVA Online Transformer-less Rack Mount UPS (External Battery)

CNBC06120CR

240VDC Rack Mount Battery Pack

COMPATIBLE ACCESSORIES

Part Number Description
CNRM0110R
Rack Mounting Rail Kit for 1-10kVA RM UPS
CNRM0110BPR
Battery Pack Rack Mounting Rail Kit for 1-10kVA RM UPS
CNS02
Mini SNMP Card